中频电源进线和出线电缆的选择参考
Information Details
中频电源进线和出线电缆的选择参考
当中频电源工作的频率为4~10kHz时,进线和出线电缆截面积应按下表的1.5倍选择电缆铜排选择表
中频电源 |
输出功率 kW |
中频频率 kHz |
输入电压 V |
进线电缆截面积mm2 |
输出铜排截面积mm2 |
槽路铜排截面积mm2 |
50 |
1-10 |
380 |
≥ 35 |
≥ 50 |
≥250 |
|
KGPS |
100 |
1-10 |
≥ 70 |
≥ 90 |
≥500 |
|
KGPS |
160 |
1-10 |
≥ 120 |
≥ 160 |
≥750 |
|
KGPS |
250 |
1-8 |
≥ 185 |
≥ 250 |
≥1500 |
|
KGPS |
350 |
1-8 |
≥ 240 |
≥ 360 |
≥1800 |
|
KGPS |
500 |
0.5-4 |
≥ 360 |
≥ 500 |
≥3000 |
|
KGPS |
750 |
0.5-4 |
≥ 500 |
≥ 720 |
≥4500 |
|
KGPS |
1000 |
0.4-4 |
660 |
≥ 360 |
≥ 500 |
≥3000 |
KGPS |
1500 |
0.4-2.5 |
≥ 500 |
≥ 720 |
≥4500 |
|
KGPS |
2000 |
0.4-2.5 |
1000 |
≥ 450 |
≥ 600 |
≥3800 |
KGPS |
3000 |
0.2-1 |
≥ 700 |
≥ 800 |
≥5000 |